Generator gas replacement must be carried out only after the generator has passed its air-tightness test and its insulation is qualified. The replacement can be performed while the rotor is stationary or running on the turning gear. This article walks through pre-checks, precautions, the startup and shutdown replacement processes, and routine hydrogen makeup.
Step 1 — Replace air with CO2:
Step 2 — Replace CO2 with hydrogen:
| Point | Requirement |
|---|---|
| Online meters | Isolate the online purity meter and humidity meter for both startup and shutdown replacement. |
| Safety | No hot work at all times; ensure ventilation; use copper tools only. |
| Differential pressure | Ensure oil-hydrogen differential pressure tracks automatically; adjust promptly if not. |
| Speed control | Control the charging and exhausting speed during replacement. |
| Purity | Purity must always meet the values specified in the operating procedures. |
Generator gas replacement must be carried out only after the generator has passed its air-tightness test and its insulation is qualified. The replacement can be performed while the rotor is stationary or running on the turning gear. This article walks through pre-checks, precautions, the startup and shutdown replacement processes, and routine hydrogen makeup.
Step 1 — Replace air with CO2:
Step 2 — Replace CO2 with hydrogen:
| Point | Requirement |
|---|---|
| Online meters | Isolate the online purity meter and humidity meter for both startup and shutdown replacement. |
| Safety | No hot work at all times; ensure ventilation; use copper tools only. |
| Differential pressure | Ensure oil-hydrogen differential pressure tracks automatically; adjust promptly if not. |
| Speed control | Control the charging and exhausting speed during replacement. |
| Purity | Purity must always meet the values specified in the operating procedures. |